Case Study - T Mobile
![]() | ![]() | |||||||||
|
The system provided by AVK|SEG (UK) LTD consisted of 2 x 825kVA Generators required to be located in the existing building in a ‘shoe horn’ fashion due to the height restriction of the premises. In addition the Generator Control Panel was located in a separate area of the building. Installation was carried out of a 30000 litre underground storage tank together with 2 x 1000 litre day tanks with transfer system.
Room attenuation was to meet 65dba at the site boundary and a separate ventilation fan was installed for temperature control set at 25 degrees centigrade. An SEG G59 Relay was fitted in the LV Switchboard as was a new Kerys controller.
This AVK|SEG (UK) LTD installation is in addition to previous projects as follows:-
T Mobile Corporate offices in Hatfield, Hertofrdshire – 2 x 375kVA Containerised Generators.